| 2003-02-25 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC 11-4.13.6WHEELCHAIR MANEUVERING |
| | CLEARANCES AT DOORS.THE PULL SIDE OF |
| | THE DOORS TO OFFICE 1 TO 6, 11 TO 18, 20 |
| | TO 21, 'ADMINISTRATOR' AND 'BREAK ROOM' |
| | SHALL HAVE A MINIMUM OF 18" CLEARANCE |
| | BETWEEN THE LEADING EDGE OF THE DOOR AND |
| | THE ADJACENT PERPENDICULAR WALL.NOTE: |
| | SHEET T-1 GENERAL DETAILS 'ACCESSIBILITY |
| | CLEARANCES' SHOW THE REQUIRED DIMENSION |
| | BUT THE RECESSES ON SHEET A-2 DO NOT |
| | APPEAR TO PROVIDE SUFFICIENT CLEARANCE |
| | WITH THE PROPOSED DOOR WIDTH.AMEND |
| | SHEET A-2 TO DIMENSION THE MINIMUM 18" |
| | CLEARNCE REQUIREMENT. |
| | |
| | 2) FBC 2405.2THE GLASS CONFERENCE ROOM |
| | DOOR IS IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).AMEND THE DOOR SCHEDULE OR |
| | PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 3) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |