| Plan Review Notes For Permit 03020423 |
| Permit Number |
03020423 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-21 00:00:00 | 1) PLEASE BE ADVISED THAT NEW STORAGE | | | AREAS ARE TO BE SEPARATED FROM OTHER | | | PORTIONS BY AT LEAST ONE HOUR FIRE | | | SEPARATION WITH 45 MINUTE OPENING | | | PROTECTIVES. | | | | | | 2) ARE NO FIRE SPRINKLERS PRESENT. | | | | | | 3) PLANS SEEM TO INDICATE THAT DOOR | | | CONTACTS AND CARD READERS ARE PRESENT | | | ON EXIT DOORS. PLEASE PROVIDE | | | ADDITIONAL INFORMATION ON HOW THESE | | | SECURITY DEVICES WILL AFFECT EXITING. | | | | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 5) IT APPEARS THAT NO EMERGENCY | | | LIGHTING IS PRESENT IN CORRIDOR NEAR | | | BYPASS WINDOW. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|