| Plan Review Notes For Permit 03020423 |
| Permit Number |
03020423 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-20 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE COMPLETE AND SHOW ALL | | | LOAD CALCULATIONS PER NEC. 220-3,220-10 | | | 220-11,220-13, ETC , PLEASE SHOW ALL | | | CONTINUOUS LOADS AT 125% PER 215-3, | | | 230-42. PLEASE SHOW A/C LOADS. | | | | | | 2)NOTE: PLEASE COMPLETE INFORMATION FOR | | | A/C UNITS ON PANEL SCHEDULE,PLEASE SHOW | | | RECEPTS PER 210-63. | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS. PLEASE ALSO CORRELATE WITH PANEL | | | SCHEDULE. PLEASE NOTE, THERE ARE SOME | | | CIRCUITS THAT DO NOT CORRELATE. | | | | | | 4)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- | | | -ING OF EM/ EXT LTS. | | | | | | 5)NOTE: PLEASE NOTE WHAT IS HAPPENING TO | | | OLD PANEL?? | | | PLEASE ALSO SEE PLAN, PLAN MENTIONS | | | EXISTING PANEL "NP" AND RISER SHOWS AS | | | BEING NEW?? PLEASE CLARIFY | | | | | | PLEASE SEE FIRE REVIEW COMMENTS THAT MAY | | | AFFECT ELECTRICAL PLANS, PLEASE ALSO | | | NOTE DUE TO SOME ITEMS NOT BEING | | | COMPLETE, THERE MAY BE OTHER COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|