Plan Review Notes
Plan Review Notes For Permit 03020418
Permit Number 03020418
Review Stop P
Sequence Number 1
Notes
Date Text
2003-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) DEMO NOTES: ALL CAPPED PLUMBING PIPES
 SHALL BE INSPECTED PRIOR TO COVERING.
 2) TABLE 403.1 DRINKING FOUNTAIN REQUIR-
 ED. ALSO SEE 410.1 (ARI-1010)
 3) SHT MP-2 ALL INDIRECT WASTE SHALL
 DRAIN TO A FLOOR SINK SEC 802.3 WITH
 A TRAP PRIMER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377