| Plan Review Notes For Permit 03020319 |
| Permit Number |
03020319 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ENERGY CALCULATIONS TO HAVE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQ'D | | | BY CHAPTER 471 FLORIDA STATUTES WHEN | | | SUBMITTING DOCUMENTS FOR PUBLIC RECORD | | | 2-PROVIDE SOIL TEST REPORT WITH ORIGINAL | | | SIGNATURE AND SEAL. CHAPTER 471 FL.ST. | | | 3-STORM SHUTTERS: SEE ENGINEERED DWGS | | | AND REVISE INSTALLATION SCHEDULE AS | | | REQUIRED. CHECK DESIGN PRESSURES, | | | PANEL MAX. SPAN, ANCHOR TYPE & SPACING | | | AND MOUNTING CONDITIONS AND CONNECTION | | | TYPE. | | | 4-SHEET A-4: SEE STAIR SECTION B/A-4 AND | | | CLARIFY NOTES #1 AND #8. SEE SECTION | | | 1007.5.1 FBC 2001. |
|