| Plan Review Notes For Permit 03020283 |
| Permit Number |
03020283 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-28 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY SHOWING | | | HOW ARE STRAPS HOLDING THE TWO GIRDER | | | TRUSSES. SECTION 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 4-REVISE/CLARIFY 34SH WINDOW SPECIFIED | | | FOR BEDROOM TO MAKE SURE IT WOULD | | | PROVIDE THE 24" MIN. CLEAR HEIGHT | | | REQUIRED BY SEC. 1005.4.4 FBC 2001. | | | ALSO, 2ND STORY BEDROOM WINDOWS TO | | | HAVE 5.7 S.F. MINIMUM CLEAR OPENING. |
|