| Plan Review Notes For Permit 03020200 |
| Permit Number |
03020200 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-20 00:00:00 | 1) PLEASE PROVIDE LIFE SAFETY PLANS FOR | | | INDUSTRIAL OCCUPANCY TO COMPLY WITH | | | NFPA 101 2000 EDITION. | | | | | | 2) FIRE PROTECTION SYSTEM IS REQUIRED | | | FOR SPRAY BOOTHS. | | | | | | 3) ALL SPRAY BOOTHS OR SPRAYING OF | | | FLAMMABLE LIQUIDS OR COMUSTIBLE MATERIAL | | | MUST COMPLY WITH NFPA 33. | | | | | | 4) MECHANICAL PLANS AND PERMITS ARE | | | REQUIRED FOR VENTILATION AND MAKE-UP AIR | | | | | | 5) ONLY 120 GAL OF FLAMMABLE LIQUIDS CAN | | | STORED IN A UL LISTED CABINET. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|