Plan Review Notes
Plan Review Notes For Permit 03020200
Permit Number 03020200
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVISIONS.
  
 1} THE RISER DIAGRAM INDICATES A 600 AMP
 METER AND 800AMP MAIN DISCONNECT,PLEASE
 CLARIFY.
  
 2} THE BOND SHOWN FROM THE METER
 ENCLOSURE TO THE GEC WOULD CREATE A
 PARALLEL GROUND PATH WITH THE GROUNDED
 NEUTRAL IN THE DISCONNECT,AND IS NOT
 NECESSARY AS THE NEUTRAL IS BONDED AT
 BOTH PIECES OF EQUIPMENT.
  
 3} PANEL "IL" IS NOT MARKED ON THE RISER
  
 4} NOTING THAT THERE ARE SPRAY BOOTHS ON
 THE PLANS ,PLEASE INDICATE CLASS &
 DIVISION FOR ALL LOCATIONS AFFECTED BY
 ARTICLES 500 THROUGH 516.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392