| Plan Review Notes For Permit 03020200 |
| Permit Number |
03020200 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO PLANS AND RESUBMIT FOR REVISIONS. | | | | | | 1} THE RISER DIAGRAM INDICATES A 600 AMP | | | METER AND 800AMP MAIN DISCONNECT,PLEASE | | | CLARIFY. | | | | | | 2} THE BOND SHOWN FROM THE METER | | | ENCLOSURE TO THE GEC WOULD CREATE A | | | PARALLEL GROUND PATH WITH THE GROUNDED | | | NEUTRAL IN THE DISCONNECT,AND IS NOT | | | NECESSARY AS THE NEUTRAL IS BONDED AT | | | BOTH PIECES OF EQUIPMENT. | | | | | | 3} PANEL "IL" IS NOT MARKED ON THE RISER | | | | | | 4} NOTING THAT THERE ARE SPRAY BOOTHS ON | | | THE PLANS ,PLEASE INDICATE CLASS & | | | DIVISION FOR ALL LOCATIONS AFFECTED BY | | | ARTICLES 500 THROUGH 516. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|