Plan Review Notes
Plan Review Notes For Permit 03020124
Permit Number 03020124
Review Stop M
Sequence Number 1
Notes
Date Text
2003-02-07 00:00:00PROVISO:MECHANICAL PERMIT 03020125
  
 RETURN AIR OR TRANSFER AIR REQUIRED FROM
 BEDROOM AREAS.2001 FBC(M) 601.4
  
 MECHANICAL EXHAUST REQUIRED FROM
 BATHROOM AS PER 2001 FBC(M) 402.3.1 &
 TABLE 403.3.
  
 EMERGENCY PAN UNDER AHU SHALL HAVE
 SECONDARY DRAIN TO A CONSPICUOUS POINT
 OR FLOAT SWITCH.2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.