| Plan Review Notes For Permit 03020124 |
| Permit Number |
03020124 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | PROVISO:MECHANICAL PERMIT 03020125 | | | | | | RETURN AIR OR TRANSFER AIR REQUIRED FROM | | | BEDROOM AREAS.2001 FBC(M) 601.4 | | | | | | MECHANICAL EXHAUST REQUIRED FROM | | | BATHROOM AS PER 2001 FBC(M) 402.3.1 & | | | TABLE 403.3. | | | | | | EMERGENCY PAN UNDER AHU SHALL HAVE | | | SECONDARY DRAIN TO A CONSPICUOUS POINT | | | OR FLOAT SWITCH.2001 FBC(M) 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|