| 2003-02-07 00:00:00 | **********CORRECTIONS************ | | | | | | 1.)PLEASE PROVIDE A DRAWING OF THE | | | FOOTPRINT OF THE HOUSE INDICATING THE | | | LOCATIONS AND SIZES OF THE OPENINGS | | | WHERE THE HURRICANE SHUTTERS ARE TO BE | | | INSTALLED. | | | | | | 2.)PLEASE INDICATE ON THE HOUSE | | | FOOTPRINT DRAWING ALL BEDROOM WINDOWS, | | | INCLUDING SIZE AND HEIGHT FROM FLOOR | | | AS PER FBC 1005.4. | | | | | | 3.)PLEASE MARK ON THE PLAN OF | | | THE HURRICANE SHUTTER INSTALLATION | | | DETAILS WHICH DETAILS WILL ACTUALLY | | | BE USED ON THIS JOB. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | LEA SMITH OR SAMANTHA THYNG | | | 561-659-8096, EXTENSION 8340 |
|