2003-05-21 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)GIVE DIMENSION OF THE WINDOW IN
 BEDROOM #1.REQUIRED TO HAVE EMERGENCY
 EGRESS FBC 1005.4.
  
 2.)PROVIDE A FRAMING DETAIL FOR THE
 NEW FRENCH DOORS.IF THE FRENCH DOORS
 ARE EXTERIOR, PROVIDE PRODUCT APPROVALS.
  
 3.)STUCCO ON METAL PLASTER BASE
 REQUIRED TO BE 7/8", FBC 2504.2,
 ASTM C 926.
  
 4.)GIVE SPACING FOR BOTTOM PLATE
 ATTACHMENT.
  
 5.)SPECIFY INSULATION IN WALLS, NOT
 "AS REQUIRED".