| 2003-03-17 00:00:00 | **************** UNSAT **************** |
| | |
| | PLEASE SEE PLANS, A COMPETELY NEW |
| | RISER DIAGRAM IS SUBMITTED. PLEASE |
| | SEE COMMENTS. |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | WERE NOT ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | NEW MAIN DISC SHOWN. PLEASE ALSO NOTE |
| | AIC RATING FOR PANEL WAS ON ORIG PLANS |
| | AND NOT SHOWN ON NEW? 110-9/215-5 |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE, THERE |
| | ARE STILL MANY ITEMS THAT DO NOT |
| | CORRELATE. PLEASE SEE OCP AND AWG. |
| | |
| | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE FOR |
| | BEDRROMS. 210-12, PLEASE VERIFY ARD |
| | FAULT NOW SHOWN FOR LIVING ROOM? |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| | PLEASE DO CALCS PER NEC 220. |
| | |
| | 5)NOTE: PLEASE SEE ORIG NOTES, WE ARE |
| | UNDER 99 NEC. |
| | |
| | 6)NOTE: PLEASE SEE 2-POLE BRKR SHOWN FOR |
| | SM APPL CIRCUIT? |
| | |
| | 7)NOTE: RISER NOW SHOWS A NEW MAIN DISC, |
| | PLEASE SEE PANEL STILL SHOWS A 200A MAIN |
| | BEING INSTALLED. PLEASE NOTE, IF A MAIN |
| | IS USED, A MCB IS NOT REQ`D AND MAY 'USE |
| | MLO? |
| | |
| | |
| | PLEASE SEE ATTACHED LETTER PER FS/ FAC |
| | 553-80(2) (B). |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |