2003-03-17 00:00:00**************** UNSAT ****************
  
 PLEASE SEE PLANS, A COMPETELY NEW
 RISER DIAGRAM IS SUBMITTED. PLEASE
 SEE COMMENTS.
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MAIN DISC SHOWN. PLEASE ALSO NOTE
 AIC RATING FOR PANEL WAS ON ORIG PLANS
 AND NOT SHOWN ON NEW? 110-9/215-5
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE, THERE
 ARE STILL MANY ITEMS THAT DO NOT
 CORRELATE. PLEASE SEE OCP AND AWG.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE FOR
 BEDRROMS. 210-12, PLEASE VERIFY ARD
 FAULT NOW SHOWN FOR LIVING ROOM?
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE DO CALCS PER NEC 220.
  
 5)NOTE: PLEASE SEE ORIG NOTES, WE ARE
 UNDER 99 NEC.
  
 6)NOTE: PLEASE SEE 2-POLE BRKR SHOWN FOR
 SM APPL CIRCUIT?
  
 7)NOTE: RISER NOW SHOWS A NEW MAIN DISC,
 PLEASE SEE PANEL STILL SHOWS A 200A MAIN
 BEING INSTALLED. PLEASE NOTE, IF A MAIN
 IS USED, A MCB IS NOT REQ`D AND MAY 'USE
 MLO?
  
  
 PLEASE SEE ATTACHED LETTER PER FS/ FAC
 553-80(2) (B).
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  