| Plan Review Notes For Permit 03020062 |
| Permit Number |
03020062 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. WATER LINES SHALL NOT | | | TIE INTO SANITARY LINES. WASHER NEEDS A | | | 2" STANDPIPE AND REQUIRES VENTING. KIT. | | | SINK NOT VENTED. DISHWASHER SHALL TIE IN | | | TO TAILPIECE UPSTREAM OF TRAP. 3" VTR | | | SHALL TIE INTO DRAIN UPSTREAM OF W/C IN | | | 2ND FLOOR BATH. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|