Plan Review Notes
Plan Review Notes For Permit 03020062
Permit Number 03020062
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-20 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 RISER DIAGRAM AND PANEL DETAIL.
 THERE ARE MANY ITEMS THAT DO NOT MATCH,
 CONDUCTORS, CONDUITS ETC.
  
 2)NOTE:PLEASE SEE PANEL SCHEDULE, THERE
 ARE MANY ITEMS, PLEASE SEE OCP AND AWG
 240-3, PLEASE SEE 20A BRKRS ON #14 AWG?
  
 3)NOTE: PLEASE SEE 210-52 FOR MIN REQ`D
 SMALL APPL CIRCUITS, PLANS SHOW NEW
 KITCHEN AND PANEL SCHEDULE ONLY SHOWS
 ONE EXISTING SM APPL CIRCUIT?? 210-11
 PLEASE ALSO SEE OTHER CIRCUTIS SHOWN
 AS EXISTING AND SHOWN AS NEW ON PLAN.
  
 4)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUITS AS #12 AND 20, 210-11-C-3
 SHOWN AS #14.
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12
  
 6)NOTE: PLANS/RISER SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR BEING INSTALLED
 BETWEEN METER AND PANEL. PLEASE SEE
 250-24, ONLY AFTER THE FIRST MEANS OF
 DISC.
  
 7)NOTE: PLEASE INCLUDE BLDG FOOTER
 STEEL AS PART OF GROUNDING ELECTRODE
 SYSTEM. 250-50.
  
 8)NOTE: PLEASE SEE NOTES LISTED, REF TO
 A 2001 NEC?
 THE 99 NEC AND THE NEXT NEC WILL BE
 2002.
  
 9)NOTE: SD MISSING AT THE BOTTOM OF
 STAIR, REQ`D PER NFPA-72 8-1.4.2
  
 10)NOTE: PLEASE RE-CONFIGURE LOAD
 CALCULATIONS TO MEET NEC ART 220.
 PLEASE NOTE, A/C LOADS MAY NOT BE
 DERATED @40% WITH LIGHTING LOADS.
  
  
 11)NOTE: PLEASE SEE 210-52D FOR OUTLET
 SPACING WITHIN 3" OF SINKS IN BATHS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372