| 2003-02-20 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE CORRELATE ELECTRICAL |
| | RISER DIAGRAM AND PANEL DETAIL. |
| | THERE ARE MANY ITEMS THAT DO NOT MATCH, |
| | CONDUCTORS, CONDUITS ETC. |
| | |
| | 2)NOTE:PLEASE SEE PANEL SCHEDULE, THERE |
| | ARE MANY ITEMS, PLEASE SEE OCP AND AWG |
| | 240-3, PLEASE SEE 20A BRKRS ON #14 AWG? |
| | |
| | 3)NOTE: PLEASE SEE 210-52 FOR MIN REQ`D |
| | SMALL APPL CIRCUITS, PLANS SHOW NEW |
| | KITCHEN AND PANEL SCHEDULE ONLY SHOWS |
| | ONE EXISTING SM APPL CIRCUIT?? 210-11 |
| | PLEASE ALSO SEE OTHER CIRCUTIS SHOWN |
| | AS EXISTING AND SHOWN AS NEW ON PLAN. |
| | |
| | 4)NOTE: PLEASE LIST THE REQ`D BATH |
| | CIRCUITS AS #12 AND 20, 210-11-C-3 |
| | SHOWN AS #14. |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12 |
| | |
| | 6)NOTE: PLANS/RISER SHOWS AN EQUIPMENT |
| | GROUNDING CONDUCTOR BEING INSTALLED |
| | BETWEEN METER AND PANEL. PLEASE SEE |
| | 250-24, ONLY AFTER THE FIRST MEANS OF |
| | DISC. |
| | |
| | 7)NOTE: PLEASE INCLUDE BLDG FOOTER |
| | STEEL AS PART OF GROUNDING ELECTRODE |
| | SYSTEM. 250-50. |
| | |
| | 8)NOTE: PLEASE SEE NOTES LISTED, REF TO |
| | A 2001 NEC? |
| | THE 99 NEC AND THE NEXT NEC WILL BE |
| | 2002. |
| | |
| | 9)NOTE: SD MISSING AT THE BOTTOM OF |
| | STAIR, REQ`D PER NFPA-72 8-1.4.2 |
| | |
| | 10)NOTE: PLEASE RE-CONFIGURE LOAD |
| | CALCULATIONS TO MEET NEC ART 220. |
| | PLEASE NOTE, A/C LOADS MAY NOT BE |
| | DERATED @40% WITH LIGHTING LOADS. |
| | |
| | |
| | 11)NOTE: PLEASE SEE 210-52D FOR OUTLET |
| | SPACING WITHIN 3" OF SINKS IN BATHS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |