| Plan Review Notes For Permit 03020062 |
| Permit Number |
03020062 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-06 00:00:00 | ****************FAILED**************** | | | ALL CONSTRUCTION MUSTCOMPLY WITH THE | | | FBC 2001 & MEET 140 MPH WIND ZONE | | | | | | 1. SUBMIT PRODUCT APPROVALS FOR THE | | | FOLLOWING: | | | A. WINDOWS | | | B. WINDOW MULLIONS | | | B. DOORS | | | C. HURRICANE PANELS* | | | D. ROOF MATERIALS | | | 2. SUBMIT 2ND COPY OF ENERGY CALCS. | | | 3. IF 2ND FLOOR WINDOWS ARE NOT IMPACT | | | SHUTTERS MUST BE CAPABLE OF BEING | | | INSTALLED FROM INTERIOR. | | | 4. SEPARATE PERMITS REQUIRED FOR FENCE | | | AND GAS. | | | 5. SUBMIT SOIL REPORT FOR NEW SLAB | | | SHOWING BEARING VALUE. | | | 6. PLANS MUST BE TAKEN TO PBC BUILDING | | | DEPARTMENT AND STAMPED AND IMPACT | | | FEES PAID BEFORE PERMIT CAN BE ISSUED | | | 7. ADDITIONAL FEES REQUIRED; CAN PAY | | | WHEN PERMIT IS ISSUED. | | | 8. PROVIDE A WINDOW SCHEDULE PRIOR TO | | | INSTALLATION.INDICATE ALL EXISTING | | | BEDROOM WINDOWS ON THE PLAN SHOWING | | | SIZES AS PER FBC 1005.4. | | | 9. DRAFTSTOPPING IS REQUIRED BETWEEN | | | FLOORS AS PER FBC 2305.2.2. | | | 10.HUGHES STRAPS SPECIFIED ARE NOT | | | AVAILABLE.PLEASE REVISE. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | PHONE: 805-6713 |
|