2003-03-06 00:00:00****************FAILED****************
 ALL CONSTRUCTION MUSTCOMPLY WITH THE
 FBC 2001 & MEET 140 MPH WIND ZONE
  
 1. SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:
 A. WINDOWS
 B. WINDOW MULLIONS
 B. DOORS
 C. HURRICANE PANELS*
 D. ROOF MATERIALS
 2. SUBMIT 2ND COPY OF ENERGY CALCS.
 3. IF 2ND FLOOR WINDOWS ARE NOT IMPACT
 SHUTTERS MUST BE CAPABLE OF BEING
 INSTALLED FROM INTERIOR.
 4. SEPARATE PERMITS REQUIRED FOR FENCE
 AND GAS.
 5. SUBMIT SOIL REPORT FOR NEW SLAB
 SHOWING BEARING VALUE.
 6. PLANS MUST BE TAKEN TO PBC BUILDING
 DEPARTMENT AND STAMPED AND IMPACT
 FEES PAID BEFORE PERMIT CAN BE ISSUED
 7. ADDITIONAL FEES REQUIRED; CAN PAY
 WHEN PERMIT IS ISSUED.
 8. PROVIDE A WINDOW SCHEDULE PRIOR TO
 INSTALLATION.INDICATE ALL EXISTING
 BEDROOM WINDOWS ON THE PLAN SHOWING
 SIZES AS PER FBC 1005.4.
 9. DRAFTSTOPPING IS REQUIRED BETWEEN
 FLOORS AS PER FBC 2305.2.2.
 10.HUGHES STRAPS SPECIFIED ARE NOT
 AVAILABLE.PLEASE REVISE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 PHONE: 805-6713