Plan Review Notes For Permit 03012458
Permit Number 03012458
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONMAKE NECESSARY CORRECTIONS
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE RISER SHOWS # 6 GEC,A #4 IS
 REQUIRED AND WAS SHOWN ON THE SERVICE
 CHANGERISER ON PREVIOUS PERMIT.
 PLEASE SHOW EXISTING RISER AS IT IS
 INSTALLED.
  
 2} CIRCUIT C-4 ON SHEET E-2 SHOWS # 14
 WIRE TO THE MASTER BATH,MUST COMPLY
 WITH 210-11(C)(3),20 AMP W/# 12 WIRE.
  
 3} CIRCUIT C-14 IN THE TOWER ROOM NOT
 SHOWN ON THE PANEL SCHEDULE.
  
 4} TOWER ROOM NEEDS A SMOKE DETECTOR TO
 COMPLY WITH 8-1.4.1.6.2(3),NFPA-72.
  
 5} MASTER BATH CIRCUITS LISTED AS C-7
 ONTHE PLAN AND BEDROOM ON PANEL
 SCHEDULE.PLAESE CORRELATE THE SCHEDULES
 WITH THE CIRCUIT LOCATIONS.
  
 6} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392