| Plan Review Notes For Permit 03012452 |
| Permit Number |
03012452 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-04 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PANEL NOT PERMITTED IN BATHROOM | | | 240-24E | | | | | | | | | 2)NOTE: PLEASE SHOW LOCATION OF SERVICE | | | AND PLEASE SEE 230-72 FOR GROUPING OF | | | MAINS. | | | | | | 3)NOTE: PLEASE SEE 210-52-C1 FOR OUTLET | | | SPACING ALONG KITCHEN COUNTERSPACE. | | | | | | 4)NOTE: RISER DIAGRAM SHOWS AN EQUIPMENT | | | GROUND BETWEEN METER AND MAIN DISC. | | | EQUIPMENT GROUNDING CONDUCTOR IS ONLY | | | INSTALLED AFTER THE FIRST MEANS OF DISC. | | | 250-24 | | | | | | 5)NOTE: PLEASE PLACE A SD IN LIVING/ | | | ADAPTABLE SLEEPING AREA ON SECONG FLOOR. | | | | | | 6)NOTE:PLEASE LIST THE REQ`D BATH | | | CIRCUIT PER 210-52D/210-11-C3, 20A,#12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 | | | EXT 8372 |
|