| 2003-02-13 00:00:00 | *********** UNSAT *********** | | | | | | 1)NOTE: PLEASE SHOW PANEL SCHEDULE FOR | | | NEW SUB PANEL. | | | PLEASE LIST THERE REQ`D ARC FAULT | | | CIRCUIT PER 210-12 | | | PLEASE LIST THE REQ`D 20A BATH CIRCUIT | | | PER 210-52D/210-11-C3 | | | PLEASE LIST ANY OTHER NEW ITEMS BEING | | | FED FROM NEW PANEL. PLEASE SHOW OCP/AWG. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | | 200A SERVICE WITH #1'S? PLEASE SEE MIN | | | REQ`MENTS FOR SEC`S. 310-15. | | | | | | 3)NOTE: PLEASE SEE CONDUCTOR SIZE | | | FEEDING NEW 80A SUB-PANEL. PLEASE SEE | | | 310-16 FOR AWG. 75 DEGREE COL. 110-14 | | | PLEASE ADJUST AWG/CONDUIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|