Plan Review Notes
Plan Review Notes For Permit 03012385
Permit Number 03012385
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-13 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SHOW PANEL SCHEDULE FOR
 NEW SUB PANEL.
 PLEASE LIST THERE REQ`D ARC FAULT
 CIRCUIT PER 210-12
 PLEASE LIST THE REQ`D 20A BATH CIRCUIT
 PER 210-52D/210-11-C3
 PLEASE LIST ANY OTHER NEW ITEMS BEING
 FED FROM NEW PANEL. PLEASE SHOW OCP/AWG.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 200A SERVICE WITH #1'S? PLEASE SEE MIN
 REQ`MENTS FOR SEC`S. 310-15.
  
 3)NOTE: PLEASE SEE CONDUCTOR SIZE
 FEEDING NEW 80A SUB-PANEL. PLEASE SEE
 310-16 FOR AWG. 75 DEGREE COL. 110-14
 PLEASE ADJUST AWG/CONDUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372