| 2003-02-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FHA-AMEND 98 DESIGN MANUAL |
| | |
| | 1) DUE TO THE NATURE OF THE JOB, ALL |
| | WORK SHALL BE CONSIDERED NEW CONSTRUCT- |
| | ION. FHA-98 WILL BE ENFORCED AT THIS |
| | TIME FOR UNITS #1, 2 & 3. PER DESIGN |
| | MANUAL, REQUIREMENTS 1 THRU 7 SHALL BE |
| | SHOWN ON PLANS. SPECIFICATION "A" OR "B" |
| | WILL BE SHOWN FOR ALL BATHROOMS. ALL |
| | CLEAR FLOOR SPACE WILL BE SUPERIMPOSED |
| | ON PLANS FOR BATHROOMS AND KITCHEN. |
| | BACKING LOCATIONS, LENGTH & HEIGHT RE- |
| | QUIREMENTS DETAIL SHALL BE SUBMITTED. |
| | 2) SHTS P-2 & P-3 FLOOR PLAN AND SANT. |
| | RISER DIAGRAM, PER SECTION 909.1 WET |
| | VENT-ONLY THE FIXTURES WITHIN THE BATH- |
| | ROOM GROUP SHALL CONNEDT TO THE WET- |
| | VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. |
| | 3) A WATER RISER DIAGRAM IS REQUIRED. |
| | SHOW ALL WATER HAMMER ARRESTORS REQUIRED |
| | BY 604.9, (WASH MACHINE, DISHWASHER, & |
| | ICE MAKER), AND LOCATED AS REFERENCED BY |
| | THIRD NOT ON SHEET P-2. |
| | 4) SHT P-3 NOTE #12, AIR CHAMBERS ARE |
| | NOT APPROVED. PLEASE DELETE FROM REFER- |
| | ENCE. |
| | |
| | REVIEW BY KEN STEVENS |