| Plan Review Notes For Permit 03012311 |
| Permit Number |
03012311 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS | | | ADDING OF NEW 400A/300A TO EXISTING | | | 400A. PLEASE SHOW SIZE OF EXSITING SEC`S | | | AND LOADS ON EXIST.215-5,220 | | | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS FOR ALL NEW FIXTURES ETC,PLEASE | | | SEE EM/EXT LTS, ALSO SEE 700-12E FOR | | | CIRCUITING. | | | | | | 3)NOTE: PLEASE PROVIDE SEPARATION ON | | | RISER DIAGRAM, SHOWN ALL AS EXISTING, | | | INCLUDING NEW PANEL "A". | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|