| Plan Review Notes For Permit 03012265 |
| Permit Number |
03012265 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-04-10 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE COMMENTS FROM | | | PREVIOUS REVIEW. | | | | | | 2)NOTE: PLEASE SIZE SERVICE ENTRANCE | | | CONDUCTOR PER 240C-3 AND 310-16,110-14 | | | | | | 3)NOTE: PLEASE SEE CIRCUITING ON PLANS. | | | PLEASE CORRELATE CIRCUIT #`S ON PLANS | | | AND PANEL SCHEDULES. PANELS SHOW MORE | | | CIRCUITS THAN SHOWN ON PLANS? | | | | | | 4)NOTE: PLEASE SEE GUTTER SIZE. 12X12X24 | | | "? PLEASE ALSO SEE 110-26A-3 GUTTER MAY | | | NOT EXTEND6" INFRONT OF ELECTRICAL | | | EQUIPMENT.? | | | | | | PLEASE SEE ABOVE COMMENTS AND SUBMIT THE | | | ABOVE INFORMATION FOR REVIEW. IF THERE | | | ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|