Plan Review Notes For Permit 03012265
Permit Number 03012265
Review Stop E
Sequence Number 3
Notes
Date Text
2003-04-10 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SIZE SERVICE ENTRANCE
 CONDUCTOR PER 240C-3 AND 310-16,110-14
  
 3)NOTE: PLEASE SEE CIRCUITING ON PLANS.
 PLEASE CORRELATE CIRCUIT #`S ON PLANS
 AND PANEL SCHEDULES. PANELS SHOW MORE
 CIRCUITS THAN SHOWN ON PLANS?
  
 4)NOTE: PLEASE SEE GUTTER SIZE. 12X12X24
 "? PLEASE ALSO SEE 110-26A-3 GUTTER MAY
 NOT EXTEND6" INFRONT OF ELECTRICAL
 EQUIPMENT.?
  
 PLEASE SEE ABOVE COMMENTS AND SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  