| 2003-03-24 00:00:00 | **************** UNSAT *************** |
| | |
| | PLEASE NOTE, NOW A COMPLETE NEW RISER |
| | DIAGRAM WAS SUBMITTED. |
| | MOST COMMENTS ARE NOW DUE TO FACT OF NEW |
| | SERVICE BEING SHOWN. |
| | |
| | 1)NOTE: PLEASE SHOW VOLTAGE OF NEW |
| | SERVICE. |
| | |
| | 2)NOTE: PLEASE CORRELATE PLANS AND RISER |
| | DIAGRAM SUBMITTED. PLANS SHOW A SEPARATE |
| | METER AND PANEL AT EACH BAY LOCATION.?? |
| | RISER SHOWS ALL COMING FROM SAME |
| | LOCATION.? |
| | |
| | 3)NOTE: PLEASE SEE 240-3C FOR SIZING |
| | OF SERVICE ENTRANCE CONDUCTORS. 310-16 |
| | |
| | 4)NOTE: PLEASE SEE NOTE FOR GROUNDING |
| | OF SERVICE TO BE AS PER FPL? PLEASE SHOW |
| | GROUNDING PER NEC REQ`D UNDER 250-50. |
| | |
| | 5)NOTE: PLEASE SEE RISER, SOME OF THE |
| | FEEDS TO BAYS ARE SHOWN COMING OUT OF |
| | METERCAN? PLEASE SHOW COMING FROM DISC`S |
| | LINE AND LOAD NOT PERMITTED IN METER |
| | ENCLOSURE. |
| | |
| | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR SERVICE. MIN TO BE SHOWN PER 220-3 |
| | ,220-10,220-11,220-13. ETC PLEASE SHOW |
| | ALL CONTINUOUS LOADS AT 125% PER 215-3 |
| | 230-42. |
| | |
| | 7)NOTE: PLEASE VERFIY SIZING OF GUTTER |
| | AND SIZE OF ELECTRICAL EQUIPMENT, IN |
| | ORDER TO MEET 110-26 FOR CLEARENCE |
| | INFRONT OF DISC`S AND METER. |
| | |
| | 8)NOTE: PLEASE SEE HOUSE PANEL SCHEDULE, |
| | SHOWS CIRCUITS FOR EM/EXT LTS, IN EACH |
| | BAY?. PLEASE NOTE, ELECTRICAL MAY NOT |
| | CROSS OVER TO OTHER BAY AREAS. |
| | PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH SUBMITTED PANEL SCHEDULES |
| | PLEASE SEE 700-12E |
| | 9)NOTE: PLEASE PROVIDE INFORMATION ON |
| | PANEL SCHEDULES? VOLTAGE/SIZE ETC ETC. |
| | |
| | 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT. MAINS/BREAKERS/PANELS |
| | ALL MUST BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. 110-9/215-5 |
| | |
| | 11)NOTE: PLEASE SEE PANEL SCHEDULES, |
| | SHOW 5 BRANCH CIRCUITS FOR LIGHTING AND |
| | LIGHTING IS NOT SHOWN ON PLANS?? |
| | |
| | 12)NOTE: PLEASE SEE PANEL SCHEDULE |
| | SHOWN AS TYPICAL,FOR UNITS 4&5, SHOWS A |
| | CARGO ELEVATOR, IS THIS IN EACH BAY? |
| | PLEASE ALSO SEE, ELEVATOR IS SHOWN AS |
| | A 1-POLE BRKR?? PLEASE VERIFY. |
| | |
| | 13)NOTE: PLEASE SEE NOTE 12 ON E-1, |
| | MENTIONS NEW SERVICE AT EACH BAY ALSO? |
| | |
| | 14)NOTE: PLEASE SEE E-1. NOTE 13 MENTION |
| | -S HOUSE PANEL TO HAVE NO LOADS EXCEPT |
| | OUTSIDE FLOODLIGHTS? AND HOUSE PANEL |
| | SHOWS OTHER LOADS AND NO FLOOD LIGHTS?? |
| | PLEASE CORRELATE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | PLEASE SEE FS/FAC 553-80(2)(B). PLEASE |
| | SEE COPY OF FS ATTACHED. |
| | |