Plan Review Notes
Plan Review Notes For Permit 03012265
Permit Number 03012265
Review Stop P
Sequence Number 1
Notes
Date Text
2003-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) MORE INFORMATION REQUIRED. WILL EACH
 UNIT BE FOR SEPARATE TENANT? IF SO THEN
 EACH UNIT WILL BE REQUIRED TO HAVE IT'S
 OWN WATER COOLER.
 2) SHT P&E-1 PLEASE SUBMIT A WATER RISER
 DIAGRAM. WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9 SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AT THE TOP OF THE DROP
 PER PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 3) SHT P&E-1 NOTE #8 AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377