| Plan Review Notes For Permit 03012265 |
| Permit Number |
03012265 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) MORE INFORMATION REQUIRED. WILL EACH | | | UNIT BE FOR SEPARATE TENANT? IF SO THEN | | | EACH UNIT WILL BE REQUIRED TO HAVE IT'S | | | OWN WATER COOLER. | | | 2) SHT P&E-1 PLEASE SUBMIT A WATER RISER | | | DIAGRAM. WATER HAMMER ARRESTORS REQUIRED | | | BY SECTION 604.9 SHALL BE LOCATED NEAR | | | THE FIXTURE IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AT THE TOP OF THE DROP | | | PER PDI-WH 201 AND MANUF. INSTALLATION | | | INSTRUCTIONS. | | | 3) SHT P&E-1 NOTE #8 AIR CHAMBERS ARE | | | NOT APPROVED. PLEASE DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|