Plan Review Notes
Plan Review Notes For Permit 03012265
Permit Number 03012265
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-02-07 00:00:001) PLEASE INDICATE WHAT BUILDING THIS
 IS AT THE SITE.
  
 2) PLEASE INDICATE OCCUPANCY TYPE AND
 EXISTING OCCUPANT LOADS.
  
 3) TREADS AND RISERS ON NEW STAIRS DO
 NOT MEET FIRE OR BUILDING CODES.
  
 4) NO INFORMATION PROVIDED WITH THE
 PLANS INDICATING IF THE BUILDING IS
 FIRE SPRINKLER PROTECTED OR NOT.
  
 5) PLEASE PROVIDE INFORMATION ON
 DEMISING WALLS LOCATED WITHIN THE
 BUILDING.
  
 6) ELECTRICAL SPECIFICATIONS MAKES
 REFERENCE TO EXIT SIGNS AND EMERGENCY
 LIGHTING. PLEASE SHOW ALL EXISTING,
 AND NEW LOCATIONS FOR THESE DEVICES.
  
 6) PLEASE PROVIDE BUILDING DATA
 INFORMATION. SIZE, CONSTRUCTION TYPE,
 ANY TENANT SEPARATIONS, TRAVEL DISTANCES
 FIRE PROTECTON, ETC.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910