| 2003-02-12 00:00:00 | ************ UNSAT *************** | | | | | | PLEASE NOTE, THERE IS NOT ENOUGH | | | ELECTRICAL INFORMATION SHOWN FOR | | | COMPLETE REVIEW. PLANS SHOW NEW METERS, | | | PANEL ETC , BUT NO RISER DIAGRAM. | | | | | | PLEASE PROVIDE SEPARATION OF UNITS IN | | | ORDER TO ADD ADDTIONAL SERVICES UNDER | | | 230-2. | | | | | | PLEASE SHOW ALL LIGHTING IN COMMON AREA | | | THAT MAY BE INSTALLED? | | | | | | PLEASE SEE ANY FIRE REVIEW COMMENTS THAT | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|