| 2003-09-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES TO | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | 2} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | 3} PLEASE NOTE THAT SMOKE DETECTORS ARE | | | TO BE INSTALLED PER 8-1.4.1.6.2 NFPA-72, | | | SHOW SAME ON PLANS. | | | | | | 4} INDICATE THE AMPERE RATING OF THE NEW | | | SERVICE. | | | | | | 5} PLEASE GIVE PANEL SCHEDULES FOR ALL | | | PANELS AND LOAD CALCULATIONS FOR THE | | | ENTIRE SERVICE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|