| 2003-02-12 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | FOR NEW AND EXISTING. PLANS SHOWS NEWW | | | AND NOTHING FOR SIZE OF EXSITING SERVICE | | | OR LOAD. 220-3-C1 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS PER 210-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EX 8372 |
|