| Plan Review Notes For Permit 03012209 |
| Permit Number |
03012209 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-10 00:00:00 | PROVISO: | | | | | | PLANS DO NOT INDICATE RATED WALLS, | | | FLOORS OR PARTITIONS.PLEASE INDICATE | | | ALL FIRE DAMPERS WHETHER NEW OR EXISTING | | | ON PLAN. | | | | | | FIRE DAMPERS SHALL BE INSTALLED IN | | | ACCORDANCE WITH MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS IN THE | | | FOLLOWING LOCATIONS. | | | 1. DUCTS PENETRATING WALLS OR PARTITIONS | | | HAVING FIRE RESISTANCE RATING OF 1 OR | | | MORE HRS. | | | 2. DUCTS PENETRATING SHAFT WALLS HAVING | | | A FIRE RESISTANCE RATING OF 1 OR MORE | | | HRS. | | | 3. DUCTS PENETRATING ONLY ONE FLOOR OF A | | | BUILDING REQUIRING THE PROTECTION OF | | | VERTICAL OPENING (FIRE DAMPER). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|