| 2003-02-11 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PLEASE CLARIFY NOTE #9 UNDER GENERAL |
| | NOTES ON SHEET 1 TO INCLUDE WINDOWS THAT |
| | ARE WITHIN THREE FEET HORIZONTALLY OF |
| | THE TUB OR SHOWER. SEE FBC 2405.2.1. |
| | |
| | 3) SPECIFY ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB IS REQUIRED TO BE |
| | SUPPORTED AT A MAXIMUM OF THREE FEET ON |
| | CENTER PER FBC 1909.3. |
| | |
| | 4) SPECIFY THE SIZES OF THE FIXED GLASS |
| | TRANSOM AND THE SIDELITE AT THE FRONT |
| | DOOR ON THE PLANS. |
| | |
| | 5) THE ROOF FRAMING PLAN ON 3A, 3B AND |
| | 3C SPECIFY AN A-5 TRUSS CONNECTOR FOR |
| | THE HIP GIRDER AT THE GARAGE. THERE IS |
| | NO A-5 CONNECTOR LISTED IN THE ANCHOR |
| | SCHEDULE ON SHEET 2. PLEASE CLARIFY. |
| | |
| | 6) PLEASE SPECIFY THE LENGTH OR EMBED |
| | DEPTH OF THE 5/8" EXPANSION BOLTS FOR |
| | THE OVERHEAD GARAGE DOOR BUCKS ON DETAIL |
| | 3 ON SHEET 4. |
| | |
| | 7) THE ENERGY CALCULATION FORM INDICATES |
| | THAT THE HVAC CREDIT FOR CEILING FANS IS |
| | BEING TAKEN. PLEASE INDICATE THE MINIMUM |
| | FAN SIZE REQUIRED FOR EACH ROOM ON THE |
| | PLANS. SEE FBC CHAPTER 13-607.1.A.1 AND |
| | TABLE 6-6. |
| | |
| | 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE ONE HOUR |
| | RATED GLASS BLOCK ASSEMBLY. |
| | |
| | 9) THE NORANDEX SITE SPECIFIC PRODUCT |
| | APPROVALS ARE REQUIRED TO BE SEALED BY |
| | THE DESIGNER OF RECORD OF THE STRUCTURE |
| | AND THE LOCATION OF THE JOB IS ALSO |
| | REQUIRED ON THE FORM. NOTE:THE SIGNATURE |
| | ON THE PRODUCT APPROVAL SUBMITTED IS |
| | FROM THE ENGINEER (STEVE WALSH), WHO HAS |
| | NOT SIGNED AND SEALED THE PLANS FOR THIS |
| | PROJECT. |
| | |
| | 10) PROVIDE A PRODUCT APPROVAL FOR THE |
| | 96"X 60" GLIDER WINDOW WITH AN XOX |
| | CONFIGURATION AS SHOWN ON THE PLANS. THE |
| | NORANDEX PRODUCT APPROVALS SUBMITTED DO |
| | NOT COVER THIS SIZE OR CONFIGURATION. |
| | |
| | 11) THE SURVEY HAS THE INCORRECT LOMR |
| | CASE NUMBER AND DATE FOR THE FLOOD ZONE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |