2004-05-08 00:00:00****** UNSAT **********
  
 1)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 MUST CONTAIN PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR PLANS.
 PRINTED NAME IS PLANS, HOWEVER, MR JUAN
 MOLINA NEEDS TO SIGN AND DATE.
  
 2)NOTE: PLEASE SEE MISSING RECEPT ON
 PLANS, ONE SHEET IS REDLINED.
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]