Plan Review Notes
Plan Review Notes For Permit 03012088
Permit Number 03012088
Review Stop E
Sequence Number 2
Notes
Date Text
2003-04-10 00:00:00************** UNSAT *********
  
 PLEASE REMOVE ALL OLD SHEETS AND INSERT
 NEW SHEETS TO MAKE TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE THE FOLLOWING COMMENTS THAT
 STILL NEED TO BE ADDRESSED FROM FIRST
 REVIEW. MOST WERE DONE.
  
 1)NOTE: PLEASE SIZE SERVICE ENTRANCE
 CONDUCTORS PER 310-15 FOR A 350A SERVICE
 INTO GUTTER. THE CONDUCTORS SHOWN FROM
 GUTTER TO MAINS ARE OK.
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE. 210-52C-1 AND
 PLEASE SHOW AS GFI/GFI PROTECTED.
 210-8A-6
 PLEASE SEE ONE SET W/ REDLINES.
  
 3)NOTE: PLEASE CALL IN REF TO PANEL "B"
 GROUNDING ELECTRODE, NOT REQ`D BUT IF
 SHOWN ON PLAN, IT WILL BE REQ`D TO BE
 INSTALLED. PLEASE CALL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. IF A VOICE MAIL IS LEFT,
 PLEASE LEAVE PHONE # FOR RETURN CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW