| Plan Review Notes For Permit 03012088 |
| Permit Number |
03012088 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-10 00:00:00 | ************** UNSAT ********* | | | | | | PLEASE REMOVE ALL OLD SHEETS AND INSERT | | | NEW SHEETS TO MAKE TWO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SEE THE FOLLOWING COMMENTS THAT | | | STILL NEED TO BE ADDRESSED FROM FIRST | | | REVIEW. MOST WERE DONE. | | | | | | 1)NOTE: PLEASE SIZE SERVICE ENTRANCE | | | CONDUCTORS PER 310-15 FOR A 350A SERVICE | | | INTO GUTTER. THE CONDUCTORS SHOWN FROM | | | GUTTER TO MAINS ARE OK. | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT FOR | | | KITCHEN COUNTERSPACE. 210-52C-1 AND | | | PLEASE SHOW AS GFI/GFI PROTECTED. | | | 210-8A-6 | | | PLEASE SEE ONE SET W/ REDLINES. | | | | | | 3)NOTE: PLEASE CALL IN REF TO PANEL "B" | | | GROUNDING ELECTRODE, NOT REQ`D BUT IF | | | SHOWN ON PLAN, IT WILL BE REQ`D TO BE | | | INSTALLED. PLEASE CALL. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. IF A VOICE MAIL IS LEFT, | | | PLEASE LEAVE PHONE # FOR RETURN CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|