Plan Review Notes
Plan Review Notes For Permit 03012088
Permit Number 03012088
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-25 00:00:00****************** UNSAT ***********
  
 1)NOTE: PLEASE SIZE SEVICE ENTRANCE
 CONDUCTORS PER 310-15. 350A SERIVCE.
 SHOWN AS 3/0`S INTO GUTTER AND 250MCM
 IN GUTTER.
  
 2)NOTE: PLEASE ALSO SIZE FEEDERS FOR
 PANELS. SHOWN AS 1/0`S FOR 200A'S?
 AND #2 FOR 150A'S. PLEASE ALSO SEE
 310-15 FOR MIN SIZE. ALSO 310-16
  
 3)NOTE: PLEASE VERIFY GROUNDING ELEC-
 -TRODE SYSTEM AT PANEL "B". PLEASE CALL.
  
 4)NOTE: PLEASE SHOW MAINS NEXT TO METER
 ON PLANS (E-2) AS SHOWN ON RISER.
  
 5)NOTE: PLEASE SEE MISSING OUTLETS
 ON ISLAND AND COUNTERSPACES IN KITCHEN.
 PER 210-52-C1,2,3,4,&5,
 ALSOPENINSULAR.
  
 6)NOTE: PLEASE ALSO SHOW ALL COUNTER-
 -SPACE RECEPTS AS GFI/GFI PROTECTED
 PER 210-8-A-6
  
 7)NOTE: PLEASE NOTE ON PLANS , ALL
 SD'S TO BE A MIN OF 3' FROM BATHS PER
 NFPA-72 8-1.4.2
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPT
 IN BATH #3. 210-52D
  
 9)NOTE: PLEASE SHOW A/C DISC'S PER
 440-11 (COND UNITS).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372