| Plan Review Notes For Permit 03012088 |
| Permit Number |
03012088 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-25 00:00:00 | ****************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SIZE SEVICE ENTRANCE | | | CONDUCTORS PER 310-15. 350A SERIVCE. | | | SHOWN AS 3/0`S INTO GUTTER AND 250MCM | | | IN GUTTER. | | | | | | 2)NOTE: PLEASE ALSO SIZE FEEDERS FOR | | | PANELS. SHOWN AS 1/0`S FOR 200A'S? | | | AND #2 FOR 150A'S. PLEASE ALSO SEE | | | 310-15 FOR MIN SIZE. ALSO 310-16 | | | | | | 3)NOTE: PLEASE VERIFY GROUNDING ELEC- | | | -TRODE SYSTEM AT PANEL "B". PLEASE CALL. | | | | | | 4)NOTE: PLEASE SHOW MAINS NEXT TO METER | | | ON PLANS (E-2) AS SHOWN ON RISER. | | | | | | 5)NOTE: PLEASE SEE MISSING OUTLETS | | | ON ISLAND AND COUNTERSPACES IN KITCHEN. | | | PER 210-52-C1,2,3,4,&5, | | | ALSOPENINSULAR. | | | | | | 6)NOTE: PLEASE ALSO SHOW ALL COUNTER- | | | -SPACE RECEPTS AS GFI/GFI PROTECTED | | | PER 210-8-A-6 | | | | | | 7)NOTE: PLEASE NOTE ON PLANS , ALL | | | SD'S TO BE A MIN OF 3' FROM BATHS PER | | | NFPA-72 8-1.4.2 | | | | | | 8)NOTE: PLEASE SEE MISSING GFI RECEPT | | | IN BATH #3. 210-52D | | | | | | 9)NOTE: PLEASE SHOW A/C DISC'S PER | | | 440-11 (COND UNITS). | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|