Plan Review Notes
Plan Review Notes For Permit 03011966
Permit Number 03011966
Review Stop P
Sequence Number 1
Notes
Date Text
2003-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) WATER COOLER SHALL COMPLY WITH ARI-
 1010. MANUF INFORMATION REQUIRED BY
 FINAL INSPECTION
 2) SHT A1 TOILET ROOMS #109 & 110, DOORS
 SHALL NOT OPEN INTO THE CLEAR FLOOR
 SPACE OF ANY FIXTURE INCLUDING THE UN-
 OBSTRUCTED 5' TURNING RADIUS. SECTIONS
 11-4.22.2, 11-4.22.3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377