| Date |
Text |
| 2003-04-16 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE SOME OF THE DESIGN CRITERA ON A5 |
| | IS NOT CORRECT. THE CITY OF WPB IS NOT |
| | IN THE HIGH VELOCITY HURRICANE ZONE. |
| | THE INTERNAL PRESSURE COEFFICENT FOR AN |
| | ENCLOSED STRUCTURE IS + OR - 0.18. |
| | THE EXPOSURE CATEGORY IS B. SEE FBC |
| | TABLES 1606.2B AND 1606.2C FOR WIND |
| | PRESSURES FOR COMPONENTS AND CLADDING. |
| | |
| | 4) CASEMENT WINDOWS IN SLEEPING ROOMS |
| | MUST COMPLY WITH FBC 1005.4 FOR |
| | EMERGENCY ESCAPE AND RESCUE. THE OFFICE |
| | WHICH COULD BE USED FOR A BEDROOM MUST |
| | COMPLY. THE MINIMUM NET CLEAR OPENING |
| | HEIGHT IS 24" AND WIDTH IS 20". THE |
| | MINIMUM NET CLEAR OPENING AREA IS 5.7 |
| | SQFT. |
| | |
| | 5) BECAUSE A FULL BATH IS PROVIDED ON |
| | HABITABLE GRADE, IT IS REQUIRED BY FBC |
| | CHAPTER 11 SECTION 11-11 TO HAVE A DOOR |
| | A 29" CLEAR OPENING. |
| | |
| | 6) THE CALCULATIONS FOR BEAM (B3) DO NOT |
| | CONSIDER THE WIND LOADS THAT WOULD BE |
| | TRANSFERED TO THE BEAM. SEE FBC 1609. |
| | PLEASE PROVIDE A COVER SHEET WITH A |
| | TITLE BLOCK (FAC 61G15-30.003) AND A |
| | SUMMARY WITH CONCLUSIONS. |
| | |
| | 7) SPECIFY THE LOCATIONS AND MATERIAL |
| | THAT WILL BE USED TO PROVIDE DRAFTSTOPP- |
| | ING AT THE FLOOR/CEILING ASSEMBLY. SEE |
| | FBC 2305.2.2. THIS IS REQUIRED AT THE |
| | FLOOR TRUSSES ON THE SECOND FLOOR NOT IN |
| | THE ATTIC. |
| | |
| | 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE PREFAB |
| | FIREPLACE AND CHIMNEY. |
| | |
| | 9) INDICATE ON THE STAIR DETAIL THE |
| | FIREBLOCKING THAT IS REQUIRED FOR THE |
| | CONCEALED SPACES OF THE STAIRS AT THE |
| | TOP AND BOTTOM OF THE RUN. FBC 2305.1.4 |
| | |
| | 10) PROVIDE DETAILS FOR THE CONSTRUCTION |
| | OF THE COLUMNS AT THE FRONT AND REAR |
| | BALCONIES TO WHICH THE GUARDRAILS ARE |
| | ATTACHED. |
| | |
| | 11) UPDATE THE CONCRETE STANDARDS IN THE |
| | NOTES ON A5 TO ACI-99. |
| | |
| | 12) PROVIDE PRODUCT APPROVALS FOR THE |
| | DOUBLE INSWING FRONT DOORS AS SHOWN ON |
| | THE PLANS. |
| | |
| | 13) THE LABELS ON THE GARAGE DOOR BUCK |
| | DETAILS ON A13 ARE REVERSED. |
| | |
| | 14) PROVIDE DETAILS OF THE TUBE STEEL |
| | COLUMN CAPS. |
| | |
| | 15) THE CONNECTOR SPECIFIED FOR THE |
| | SECOND FLOOR ROOF GIRDER TRUSS(T27,2PLY) |
| | IS INCORRECT. THIS TRUSS SITS ON TOP OF |
| | THE TIE BEAM AND A SIMPSON MBHA, WHICH |
| | IS A HANGER, IS SPECIFIED. |
| | |
| | 16) THE UPLIFT VALUES SPECIFIED ON THE |
| | PLANS FOR MOST OF THE ROOF GIRDER |
| | TRUSSES ARE LOWER THAN REQUIRED BY THE |
| | TRUSS DRAWINGS. THE CONNECTORS AS |
| | SPECIFIED WILL NOT BE CAPABLE OF |
| | RESISTING THE REQUIRED LOADS. |
| | |
| | 17) THE NEW PLANS WILL HAVE TO BE |
| | RTEVIEWED AND APPROVED BY THE HISTORIC |
| | PRESERVATION BEFORE PERMIT IS ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |