Plan Review Notes
Plan Review Notes For Permit 03011850
Permit Number 03011850
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-11 00:00:00************ UNSAT ****************
  
 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 8-1.4.2
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAY.
 3'FT FROM BATHS/KITCHENS.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5 ) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 6 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 7)NOTE: PLEASE SHOW BATHS PER 210-52D
 210-11-C3
  
 8)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 SHOWING ALL MIN REQ`D CIRCUITS PER
 210-52/210-11 ECT.
  
 PLEASE COMPLETE PLANS AND SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372