| Plan Review Notes For Permit 03011841 |
| Permit Number |
03011841 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-25 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-REVISE LOCATION FOR SOIL TEST REPORT. | | | THIS IS LOT 227, PARCEL F. NOT PARCEL | | | G. | | | 2-STORM SHUTTERS: PROVIDE COMPLETE AND | | | CORRECT INFORMATION: | | | A)SITE SPECIFIC PRODUCT APPROVAL NEEDS | | | THE APPROVATION OF DESIGNER OF RECORD, | | | AS REQ'D BY THE BUILDING OFFICIAL. | | | B)NEED "CERTIFICATE OF COMPLIANCE" AND | | | INSTALLATION AFFIDAVIT" FOR SITE | | | SPECIFIC STORM SHUTTERS AS REQUIRED BY | | | THE CITY IMPLEMENTATION STANDARD FOR | | | HURRICANE MISSILE IMPACT PROTECTION. | | | C)REVISE/CLARIFY WHY INSTALLATION SCHED. | | | AND KEY PLAN CALLS FOR SBCCI PRODUCT | | | APPROVAL BUT DRAWINGS SUBMITTED ARE | | | FOR SITE SPECIFIC ENGINEERING. | | | D)REVISE INSTALLATION SCHEDULE TO MATCH | | | ENGINEERING DRAWINGS: CHECK THE DESIGN | | | PRESSURES, MINIMUM AND MAXIMUM SHUTTER | | | LENGTH ALLOWED, AND ANCHOR SPACING. |
|