| Plan Review Notes For Permit 03011809 |
| Permit Number |
03011809 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-19 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY. HOW ARE | | | GIRDER TRUSSES SUPPORTED?. SEE 2ND FL | | | FRAMING PLAN. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 4-REVISE CONNECTOR TC-1 SPECIFIED ON | | | ROOF FRAMING PLAN @ FRAMED WALL ON | | | FRONT ELEVATION. NEED WOOD TO WOOD | | | CONNECTORS. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 5-34SH WINDOW DOESN'T PROVIDE THE 24" | | | CLEAR HEIGHT REQUIRED BY SEC. 1005.4.4 | | | FBC 2001. REVISE CLARIFY AS REQUIRED. | | | 6-PROVIDE SOIL TEST REPORT PRIOR TO | | | CONSTRUCTION. |
|