| Plan Review Notes For Permit 03011787 |
| Permit Number |
03011787 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-10 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE CORRELATE OCP/AWG WITH | | | RISER DIAGRAM. PANEL SHOWS #10 AND 40A | | | FOR 60A SUB PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|