Plan Review Notes
Plan Review Notes For Permit 03011631
Permit Number 03011631
Review Stop E
Sequence Number 2
Notes
Date Text
2003-04-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE FOLLOWING CORRECTIONS WERE NOT MADE
 FROM THE LAST REVIEW,PLEASE CORRECT
 AND RESUBMIT FOR REVIEW.
  
 1} THE GEC TO THE GROUND ROD IS THE
 CORRECT SIZE BUT MUST BE CONTINUOUS PER
 250-64,TO THE FOOTER STEEL,GROUND ROD
 AND COLD WATER PIPE.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} THE GFI IN THE MASTER BATH MUST
 COMPLY WITH 210-52(D).OR ADD ONE TO
 COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718