| Plan Review Notes For Permit 03011631 |
| Permit Number |
03011631 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE FOLLOWING CORRECTIONS WERE NOT MADE | | | FROM THE LAST REVIEW,PLEASE CORRECT | | | AND RESUBMIT FOR REVIEW. | | | | | | 1} THE GEC TO THE GROUND ROD IS THE | | | CORRECT SIZE BUT MUST BE CONTINUOUS PER | | | 250-64,TO THE FOOTER STEEL,GROUND ROD | | | AND COLD WATER PIPE. | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} THE GFI IN THE MASTER BATH MUST | | | COMPLY WITH 210-52(D).OR ADD ONE TO | | | COMPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|