| 2003-04-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE INFORMATION FOR ALL |
| | EXTERIOR DOORS AND WINDOWS, STOREFRONT |
| | SYSTEM AT LIVING ROOM, CUSTOM MADE |
| | ENTRY DOOR AND GARAGE DOORS UNDERA |
| | SEPARATE PERMIT. |
| | 2-MAKE SURE THAT BEDROOM EGRESS WINDOWS |
| | HAVE 20" MIN. CLEAR WIDTH OPENING AS |
| | REQUIRED BY SEC. 1005.4 FBC 2001. |
| | |
| | 3-PROVIDE COMPLETE UL LISTING AND SPECS |
| | FOR VENTLESS FIREPLACE. |
| | NEED TO MEET THE REQUIREMENTS OF UL127 |
| | AS REQUIRED BY SEC. 2806.1 FBC 2001. |
| | 4-THERE MUST BE A COMPLETE BATHROOM WITH |
| | DOOR ALLOWING 29" MIN. CLEAR OPENING. |
| | AS REQUIRED BY SEC. 11 CHAPTER 11 FBC. |
| | 5-ENGINEERED FLOOR SYSTEM TO BE REVIEWED |
| | AND APPROVED BY ARCHITECT/ENGINEER OF |
| | RECORD (USE STANDARD REVIEW STAMP) |
| | PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | 6-PROVIDE DETAIL/SPECS FOR CONNECTIONS |
| | OF TOP OF STEEL COLUMN TO CONCRETE |
| | BEAM. SEE FRAMING PLANS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-REVISE STRUCTURAL 2X BUCK DETAIL TO |
| | COMPLY WITH SEC. 1707.4.4.2 FBC 2001. |
| | 8-REVISE ROOF SHEATHING INSTALLATION |
| | SCHEDULE. SEE TABLE 2306.1 OF CITY |
| | AMENDEMNTS TO FBC 2001. NEED 8D RING |
| | SHANK NAILS ABOVE 25' FOR ZONE 3. |
| | 9-SPECIFY 6MIL MINIMUM VAPOR BARRIER AT |
| | FOUNDATION PLAN AS REQUIRED BY SECTION |
| | 1909.2 FBC 2001. |