Plan Review Notes
Plan Review Notes For Permit 03011631
Permit Number 03011631
Review Stop B
Sequence Number 2
Notes
Date Text
2003-04-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR ALL
 EXTERIOR DOORS AND WINDOWS, STOREFRONT
 SYSTEM AT LIVING ROOM, CUSTOM MADE
 ENTRY DOOR AND GARAGE DOORS UNDERA
 SEPARATE PERMIT.
 2-MAKE SURE THAT BEDROOM EGRESS WINDOWS
 HAVE 20" MIN. CLEAR WIDTH OPENING AS
 REQUIRED BY SEC. 1005.4 FBC 2001.
  
 3-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR VENTLESS FIREPLACE.
 NEED TO MEET THE REQUIREMENTS OF UL127
 AS REQUIRED BY SEC. 2806.1 FBC 2001.
 4-THERE MUST BE A COMPLETE BATHROOM WITH
 DOOR ALLOWING 29" MIN. CLEAR OPENING.
 AS REQUIRED BY SEC. 11 CHAPTER 11 FBC.
 5-ENGINEERED FLOOR SYSTEM TO BE REVIEWED
 AND APPROVED BY ARCHITECT/ENGINEER OF
 RECORD (USE STANDARD REVIEW STAMP)
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 6-PROVIDE DETAIL/SPECS FOR CONNECTIONS
 OF TOP OF STEEL COLUMN TO CONCRETE
 BEAM. SEE FRAMING PLANS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE STRUCTURAL 2X BUCK DETAIL TO
 COMPLY WITH SEC. 1707.4.4.2 FBC 2001.
 8-REVISE ROOF SHEATHING INSTALLATION
 SCHEDULE. SEE TABLE 2306.1 OF CITY
 AMENDEMNTS TO FBC 2001. NEED 8D RING
 SHANK NAILS ABOVE 25' FOR ZONE 3.
 9-SPECIFY 6MIL MINIMUM VAPOR BARRIER AT
 FOUNDATION PLAN AS REQUIRED BY SECTION
 1909.2 FBC 2001.