2003-03-17 00:00:00PROVISO
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 ELECTRICAL INSPECTION.
  
 1} THE GEC IS INCORRECT FOR A 400 AMP.
 SERVICE,SEE 250-66.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} THE RECEPTACLE IN THE CABANA BATH
 SHOULD BE GFI PER 210-8.
  
 5} PLEASE CORRECT THE CALCULATION FOR
 THE POOL PANEL,SHOWN AS 1.8 VA.
  
 6} PLEASE NOTE THE RECEPTACLE SPACING IN
 THE MUSIC ROOM NEEDS TO COMPLY WITH
 210-52.
  
 7} WHERE IS THE POOL EQUIPMENT PANEL
 LOCATED?
  
 8} THE GFI IN THE MASTER BATH MUST
 COMPLY WITH 210-52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561-8096 EXT.8392