| Plan Review Notes For Permit 03011631 |
| Permit Number |
03011631 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-17 00:00:00 | PROVISO | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | ELECTRICAL INSPECTION. | | | | | | 1} THE GEC IS INCORRECT FOR A 400 AMP. | | | SERVICE,SEE 250-66. | | | | | | 2} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 3} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 4} THE RECEPTACLE IN THE CABANA BATH | | | SHOULD BE GFI PER 210-8. | | | | | | 5} PLEASE CORRECT THE CALCULATION FOR | | | THE POOL PANEL,SHOWN AS 1.8 VA. | | | | | | 6} PLEASE NOTE THE RECEPTACLE SPACING IN | | | THE MUSIC ROOM NEEDS TO COMPLY WITH | | | 210-52. | | | | | | 7} WHERE IS THE POOL EQUIPMENT PANEL | | | LOCATED? | | | | | | 8} THE GFI IN THE MASTER BATH MUST | | | COMPLY WITH 210-52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561-8096 EXT.8392 |
|