Plan Review Notes
Plan Review Notes For Permit 03011631
Permit Number 03011631
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-31 00:00:00BUILDING REVIEW CHECKLIST:
 1-HOUSE LOCATED ON FLOOD ZONE A5. FIN.
 FLOOR ELEVATION TO BE 7'-6" MIN. AS
 REQ'D BY CHAPTER 12 OF CITY CODE.
 CLEARLY SHOW ON SURVEY AND FLOOR PLANS
 THE PROPOSED FIN. FLOOR ELEVATION.
 2-SURVEY DOESN'T MATCH FLOOR PLANS.
 OUTDOOR ENTERTAINMENT IS NOT SEPARATED
 FROM THE HOUSE. SEE PLANS AND REVISE.
 3-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-PROVIDE SOIL TEST REPORTS W/ ORIGINAL
 SIGNATURES AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 6-PROVIDE ALL INFORMATION AS REQUIRED BY
 SEC. 1606.1.7 FBC 2001. ***NOTE: THERE
 ARE 5 ITEMS LISTED. PROVIDE ALL FIVE.
 7-A)NEED COMPLETE INFORMATION FOR PILE
 SYSTEM TO BE USED. SEE SECTIONS 1805
 THRU 1813 FBC 2001 FOR REQ'D DESIGN
 INFORMATION AND INSTALLATION.
 B)ENGINEER TO SIGN ALL SHEETS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 C)DESIGNER OF RECORD TO REVIEW & APPROVE
 THIS DELEGATED DESIGN.(REVIEWED STAMP)
 D)PILING PLAN DOESN'T MATCH DESIGNER'S
 OF RECORD FOUNDATION PLAN. REVISE/
 CLARIFY AS REQUIRED.
 8-DOORS/WINDOWS ARE TO HAVE IMPACT GLASS
 OR STORM SHUTTERS. PROVIDE PRODUCT
 APPROVAL FOR DOORS/WINDOWS OR COMPLETE
 INFO. FOR STORM SHUTTERS INCLUDING KEY
 PLAN AND COMPLETE INSTALLATION SCHED.
 (SEE CITY SAMPLE). ALSO, MARK ON DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING ACCORDING TO DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO.
 9-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SEC. 2405.2 FBC 2001.
 10-BEDROOM EGRESS WINDOWS NEED 20" MIN.
 CLEAR WIDTH OPENING. CLARIFY IF CASE-
 MENT WINDOWS PROVIDE THIS CLEARANCE.
 11-PROVIDE PRODUCT APPROVAL FOR: A)ENTRY
 DOOR. 4'X11' WITH ROUND TOP AS SHOWN
 ON PLANS. B)ROOF TILE. C)FRENCH DOORS
 WITH TRANSOM ABOVE SINGLE ASSEMBLY AS
 SHOWN ON PLANS. D)CASEMENT WINDOWS.
 E)WINDOWS AND DOORS MULLIONS. F)BBQ
 UL LISTING AND SPECS. G)FIREPLACE UL
 LISTING AND SPECS. H)FIXED WINDOWS AS
 SHOWN ON PLANS. I)STOREFRONT SYSTEM AS
 SHOWN ON PLANS. J)ARCHED WINDOWS.
 K)ROUND WINDOWS.
 12-PROVIDE COMPLETE AHU HANGING DETAIL.
 SPECIFY BOLTS AND CHAIN SIZE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-PROVIDE COMPLETE BATHROOM IN FIRST
 FLOOR WITH DOOR THAT ALLOWS 29" MIN.
 CLEAR OPENING. SEC. 11 OF CHAPTER 11
 FBC 2001.
 14-PROVIDE COMPLETE STAIR DETAILS AND
 SECTIONS. SEE SEC. 1007.8.3 FOR CIRCU-
 LAR STAIR REQUIREMENTS.
 **ALSO SEE SEC. 1007.5.1 AND 1015.3 FOR
 HEIGHT AND CLEARANCES.
 **SEE SEC. 1606.8.2 FOR RAILING DESIGN.
 15-PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 BY THE STAIRWAY AS REQUIRED BY SECTION
 905.2.2 FBC 2001.
 16-PROVIDE COMPLETE ENGINEERING PACKAGE
 AND SPECIFICATIONS FOR HAMBRO FLOOR
 SYSTEM. NOTE: DESIGNER OF RECORD TO
 REVIEW ALL INFO. PRIOR TO SUBMITTAL
 17-PROVIDE ATTIC ACCESS AT SECONF FLOOR
 ROOF AND AT ROOF ABOVE GARAGE AS REQ'D
 BY SEC. 2309.6 FBC 2001.
 18-PROVIDE VENTILATION AT ATTIC AREA AS
 REQ'D BY SEC. 2309.7 FBC 2001.
 19-PROVIDE DETAILS/SPECS FOR CONNECTIONS
 AT TOP OF STEEL COLUMNS. SEE PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 20-SHEET S-4: SPECIFY ALL BEAMS AND
 CONNECTORS. SEE PLANS FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 21-PROVIDE COMPLETE DETAILS & SPECS FOR
 STRUCTURAL LEDGERS. SEE PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 22-PROVIDE COMPLETE FIREPLACE STRUCTURAL
 SECTION. INCLUDING CHIMNEY. SPECIFY
 ALL FASTENERS. SHOW CHIMNEY ON EXT.
 ELEVATIONS. SEC. 2804 FBC 2001 & SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 23-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECS FOR WOOD TRELLIS.SPECIFY ALL
 FASTENERS. SEC. 104.2.1.2 CITY AMEND.
 24-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CEILING INSTALLATION AT FRONT AND
 REAR PORCHES. SPECIFY FASTENERS AS
 REQ'D BY ASTM C-926 AND ASTM C-1063.
 25-REVISE 2X STRUCTURAL BUCK DETAIL FOR
 DOOR. SEE SEC. 1707.4.4.2 FBC 2001 FOR
 SPECIFIC INSTALLATION REQUIREMENTS.
 26-PROVIDE ROOF SHEATHING SCHEDULE. SEE
 SEC. 2306.1 CITY AMENDMENTS TO FBC.
 27-SPECIFY WWM SUPPORTS AND SPACING AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 28-OWES $497.64 FOR UPDATED VALUATION
 AND RADON FEES.
 29-SEE REVIEWED SET OF PLANS FOR ADDITIO
 NAL COMMENTS/CLARIFICATIONS AND RETURN
 REVIEWED SET AFTER CORRECTIONS ARE DONE
 TO ORIGINAL CAD DRAWINGS TO EXPEDITE
 THE REVIEW PROCESS.
 30-REVISE ENERGY CALCS: A)A/C AREA DOES
 NOT MATCH PLANS. B)WALL TYPE SPECIFIED
 IS INCORRECT. SEE PLANS FOR ADJACENT
 WALL. C)OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM AS WELL. D)COMPLETE ALL
 INFORMATION ON TOP OF FORM.
 31-IF TAKING CEILING FANS CREDIT, THEN
 NEED TO SHOW THEM IN PLANS. SEE TABLE
 6-6 OF CHAPTER 13 FBC 2001 FOR REQUIRED
 SIZES AND NUMBER.