| 2003-03-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-HOUSE LOCATED ON FLOOD ZONE A5. FIN. |
| | FLOOR ELEVATION TO BE 7'-6" MIN. AS |
| | REQ'D BY CHAPTER 12 OF CITY CODE. |
| | CLEARLY SHOW ON SURVEY AND FLOOR PLANS |
| | THE PROPOSED FIN. FLOOR ELEVATION. |
| | 2-SURVEY DOESN'T MATCH FLOOR PLANS. |
| | OUTDOOR ENTERTAINMENT IS NOT SEPARATED |
| | FROM THE HOUSE. SEE PLANS AND REVISE. |
| | 3-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACK STAMPED DRAWINGS & RECEIPT. |
| | 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 5-PROVIDE SOIL TEST REPORTS W/ ORIGINAL |
| | SIGNATURES AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | 6-PROVIDE ALL INFORMATION AS REQUIRED BY |
| | SEC. 1606.1.7 FBC 2001. ***NOTE: THERE |
| | ARE 5 ITEMS LISTED. PROVIDE ALL FIVE. |
| | 7-A)NEED COMPLETE INFORMATION FOR PILE |
| | SYSTEM TO BE USED. SEE SECTIONS 1805 |
| | THRU 1813 FBC 2001 FOR REQ'D DESIGN |
| | INFORMATION AND INSTALLATION. |
| | B)ENGINEER TO SIGN ALL SHEETS AS REQ'D |
| | BY CHAPTER 471 FLORIDA STATUTES. |
| | C)DESIGNER OF RECORD TO REVIEW & APPROVE |
| | THIS DELEGATED DESIGN.(REVIEWED STAMP) |
| | D)PILING PLAN DOESN'T MATCH DESIGNER'S |
| | OF RECORD FOUNDATION PLAN. REVISE/ |
| | CLARIFY AS REQUIRED. |
| | 8-DOORS/WINDOWS ARE TO HAVE IMPACT GLASS |
| | OR STORM SHUTTERS. PROVIDE PRODUCT |
| | APPROVAL FOR DOORS/WINDOWS OR COMPLETE |
| | INFO. FOR STORM SHUTTERS INCLUDING KEY |
| | PLAN AND COMPLETE INSTALLATION SCHED. |
| | (SEE CITY SAMPLE). ALSO, MARK ON DWGS |
| | SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| | TYPE AND SPACING ACCORDING TO DESIGN |
| | PRESSURES, EDGE DISTANCE, PANEL SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO. |
| | 9-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS. SEC. 2405.2 FBC 2001. |
| | 10-BEDROOM EGRESS WINDOWS NEED 20" MIN. |
| | CLEAR WIDTH OPENING. CLARIFY IF CASE- |
| | MENT WINDOWS PROVIDE THIS CLEARANCE. |
| | 11-PROVIDE PRODUCT APPROVAL FOR: A)ENTRY |
| | DOOR. 4'X11' WITH ROUND TOP AS SHOWN |
| | ON PLANS. B)ROOF TILE. C)FRENCH DOORS |
| | WITH TRANSOM ABOVE SINGLE ASSEMBLY AS |
| | SHOWN ON PLANS. D)CASEMENT WINDOWS. |
| | E)WINDOWS AND DOORS MULLIONS. F)BBQ |
| | UL LISTING AND SPECS. G)FIREPLACE UL |
| | LISTING AND SPECS. H)FIXED WINDOWS AS |
| | SHOWN ON PLANS. I)STOREFRONT SYSTEM AS |
| | SHOWN ON PLANS. J)ARCHED WINDOWS. |
| | K)ROUND WINDOWS. |
| | 12-PROVIDE COMPLETE AHU HANGING DETAIL. |
| | SPECIFY BOLTS AND CHAIN SIZE. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 13-PROVIDE COMPLETE BATHROOM IN FIRST |
| | FLOOR WITH DOOR THAT ALLOWS 29" MIN. |
| | CLEAR OPENING. SEC. 11 OF CHAPTER 11 |
| | FBC 2001. |
| | 14-PROVIDE COMPLETE STAIR DETAILS AND |
| | SECTIONS. SEE SEC. 1007.8.3 FOR CIRCU- |
| | LAR STAIR REQUIREMENTS. |
| | **ALSO SEE SEC. 1007.5.1 AND 1015.3 FOR |
| | HEIGHT AND CLEARANCES. |
| | **SEE SEC. 1606.8.2 FOR RAILING DESIGN. |
| | 15-PROVIDE SMOKE DETECTOR AT FIRST FLOOR |
| | BY THE STAIRWAY AS REQUIRED BY SECTION |
| | 905.2.2 FBC 2001. |
| | 16-PROVIDE COMPLETE ENGINEERING PACKAGE |
| | AND SPECIFICATIONS FOR HAMBRO FLOOR |
| | SYSTEM. NOTE: DESIGNER OF RECORD TO |
| | REVIEW ALL INFO. PRIOR TO SUBMITTAL |
| | 17-PROVIDE ATTIC ACCESS AT SECONF FLOOR |
| | ROOF AND AT ROOF ABOVE GARAGE AS REQ'D |
| | BY SEC. 2309.6 FBC 2001. |
| | 18-PROVIDE VENTILATION AT ATTIC AREA AS |
| | REQ'D BY SEC. 2309.7 FBC 2001. |
| | 19-PROVIDE DETAILS/SPECS FOR CONNECTIONS |
| | AT TOP OF STEEL COLUMNS. SEE PLANS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 20-SHEET S-4: SPECIFY ALL BEAMS AND |
| | CONNECTORS. SEE PLANS FOR COMMENTS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 21-PROVIDE COMPLETE DETAILS & SPECS FOR |
| | STRUCTURAL LEDGERS. SEE PLANS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 22-PROVIDE COMPLETE FIREPLACE STRUCTURAL |
| | SECTION. INCLUDING CHIMNEY. SPECIFY |
| | ALL FASTENERS. SHOW CHIMNEY ON EXT. |
| | ELEVATIONS. SEC. 2804 FBC 2001 & SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 23-PROVIDE COMPLETE FRAMING DETAILS AND |
| | SPECS FOR WOOD TRELLIS.SPECIFY ALL |
| | FASTENERS. SEC. 104.2.1.2 CITY AMEND. |
| | 24-PROVIDE COMPLETE DETAILS AND SPECS |
| | FOR CEILING INSTALLATION AT FRONT AND |
| | REAR PORCHES. SPECIFY FASTENERS AS |
| | REQ'D BY ASTM C-926 AND ASTM C-1063. |
| | 25-REVISE 2X STRUCTURAL BUCK DETAIL FOR |
| | DOOR. SEE SEC. 1707.4.4.2 FBC 2001 FOR |
| | SPECIFIC INSTALLATION REQUIREMENTS. |
| | 26-PROVIDE ROOF SHEATHING SCHEDULE. SEE |
| | SEC. 2306.1 CITY AMENDMENTS TO FBC. |
| | 27-SPECIFY WWM SUPPORTS AND SPACING AS |
| | REQUIRED BY SEC. 1909.3 FBC 2001. |
| | 28-OWES $497.64 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | 29-SEE REVIEWED SET OF PLANS FOR ADDITIO |
| | NAL COMMENTS/CLARIFICATIONS AND RETURN |
| | REVIEWED SET AFTER CORRECTIONS ARE DONE |
| | TO ORIGINAL CAD DRAWINGS TO EXPEDITE |
| | THE REVIEW PROCESS. |
| | 30-REVISE ENERGY CALCS: A)A/C AREA DOES |
| | NOT MATCH PLANS. B)WALL TYPE SPECIFIED |
| | IS INCORRECT. SEE PLANS FOR ADJACENT |
| | WALL. C)OWNER/AGENT TO SIGN AND DATE |
| | BOTTOM OF FORM AS WELL. D)COMPLETE ALL |
| | INFORMATION ON TOP OF FORM. |
| | 31-IF TAKING CEILING FANS CREDIT, THEN |
| | NEED TO SHOW THEM IN PLANS. SEE TABLE |
| | 6-6 OF CHAPTER 13 FBC 2001 FOR REQUIRED |
| | SIZES AND NUMBER. |