| 2003-05-08 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLANS FOR CODE COMPLIANCE,AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} NOTE THE #2 FEEDER SHOWN IS ONLY | | | RATED FOR 125 AMPS.PLEASE CHECK THE | | | SIZE AT THE SERVICE AND IF THE CORRECT | | | SIZE IS #2 THE MAIN BREAKER MUST BE | | | CHANGED TO 125 AMPS,OR THE SERVICE MUST | | | BE UPGRADED TO 200 AMPS WITH 2/0 WIRE. | | | | | | 2} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ'D PER 210-52E | | | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5.ALSO SHALL BE GFI | | | PROTECTED PER 210-8(A)(6),LIST SAME ON | | | PLANS. | | | | | | 4} THE RECEPTACLE SPACING IN THE | | | FAMILY,OFFICE AND MASTER BEDROOMS MUST | | | COMPLY WITH 210-52. SEE REDLINED PLANS. | | | | | | 5} THERE MUST BE A RECEPTACLE IN THE | | | MASTER BATH TO COMPLY WITH 210-52(D). | | | | | | 6} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S), PER 210-11-C-3 | | | MUST BE 20A AND #12AWG,ON PANEL | | | SCHEDULE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|