Plan Review Notes
Plan Review Notes For Permit 03011556
Permit Number 03011556
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-28 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE PROVIDE LOAD CALCULATION
 FOR NEW CIRCUITS/EQUIPMENT BEING ADDED.
 PLEASE SHOW NEW TRK LIGHTING PER 220-12
 AND SHOW ALL CONTINUOUS LOADS AT 125%
 215-3,230-42 ETC.
  
 2)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 TO CORRELATE WITH NEW CIRCUITS AND SHOW
 NEW CIRCUTIS ON PLANS/FLOOR LAYOUT.
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 MAY OR MAY-NOT AFFECT ELECTRICAL PLANS.
 VERIFY EM LTS AND EXT LTS. 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARENY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372