Plan Review Notes
Plan Review Notes For Permit 03011384
Permit Number 03011384
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-28 00:00:00**********UNSAT ******************
  
 1)NOTE: PLEASE NOTE, PANEL IS SHOWN
 BEHIND DESK AREA ON PLAN. IT IS NOTED
 THAT "DESK IS MOVABLE" . PLEASE NOTE
 PER NEC 110-26 WORKING CLEARENCES ARE
 ALL THE TIME. PLEASE ADJUST FURNITURE
 LAYOUT TO MEET 110-26.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 2)NOTE: PLEASE SUBMIT/SHOW AIC RATING
 FOR NEW MAIN DISCONNECT. 110-9