| Plan Review Notes For Permit 03011384 |
| Permit Number |
03011384 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-28 00:00:00 | **********UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE, PANEL IS SHOWN | | | BEHIND DESK AREA ON PLAN. IT IS NOTED | | | THAT "DESK IS MOVABLE" . PLEASE NOTE | | | PER NEC 110-26 WORKING CLEARENCES ARE | | | ALL THE TIME. PLEASE ADJUST FURNITURE | | | LAYOUT TO MEET 110-26. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 2)NOTE: PLEASE SUBMIT/SHOW AIC RATING | | | FOR NEW MAIN DISCONNECT. 110-9 |
|