| Plan Review Notes For Permit 03011382 |
| Permit Number |
03011382 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CORRECTIONS | | | TO PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE PROVIDE A LOAD CALCULATION FOR | | | THE 225 AMP PANEL FEEDING THE NEW | | | EQUIPMENT,INCLUDING EXISTING LOADS. | | | | | | 2} NOTE THE DICREPANCIES IN | | | TRANSFORMER,PANEL AND DISCONNECT | | | RATINGS FOR THE NEW EQUIPMENT ON THE 2 | | | SETS OF PLANS SUBMITED.PLEASE CORRELATE | | | TO SHOW ACTUAL VALUES OF THE EQUIPMENT | | | TO BE INSTALLED. | | | | | | 3} THE FEEDER SIZES FOR "B","C","D" AND | | | "E"RUNS ON THE RISER ARE ALSO DIFFERENT | | | ON THE 2 SHEETS SUBMITTED,PLEASE | | | CORRELATE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392. |
|