2003-02-13 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE AND KITCHEN. CLARIFY
 HOW ARE STRAPS HOLDING THE GIRDER
 TRUSSES. SEE FLOOR FRAMING PLAN. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: SPECIFY ALL CONNECTORS.
 ROOF FRAMING PLAN DOESN'T SPECIFY THEM
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-GARAGE DOOR STRUCTURAL BUCK DETAIL:
 SPECIFY ANCHOR EMBEDMENT AND WASHER
 SIZE. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 11-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.