| Plan Review Notes For Permit 03011248 |
| Permit Number |
03011248 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-29 00:00:00 | PAID PLAN REVIEW NOT A PERMIT | | | APPLICATION. | | | | | | SHEET A4.THE SIMPLIFIED PROCEDURES OF | | | FBC 1606.2 ARE NOT APPLICBLE TO THIS | | | PROPOSED BUILDING AS THE MEAN ROOF | | | HEIGHT EXCEEDS THE LEAST HORIZONTAL | | | DIMENSION. | | | PROVIDE CALCULATIONS IN ACCORDANCE WITH | | | ASCE 7-98 AT TIME OF PERMIT APPLICATION. | | | | | | THE PLANS DO NOT SHOW THE ATTIC ACCESS | | | AND ATTIC VENTILATION IN ACCORCANCE | | | WITH FBC 2309.6 & 2309.7. | | | | | | DESIGN LOADS FOR THE FLOOR TRUSSES ARE | | | NOT SHOWN. | | | | | | SECTION B/A3 SHOWS A 1 1/2" THRESHOLD AT | | | THE SECOND FLOOR STAIR - DOOR. A | | | MAXIMUM 1/2" IS ALLOWED BY FBC 1012.1.3. | | | | | | THE OPENING BENEATH THE EXTERIOR STAIR | | | IS REQUIRED TO BE FIRE RATED BY FBC | | | 1006.2.4. |
|