Plan Review Notes
Plan Review Notes For Permit 03011248
Permit Number 03011248
Review Stop B
Sequence Number 1
Notes
Date Text
2003-01-29 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 SHEET A4.THE SIMPLIFIED PROCEDURES OF
 FBC 1606.2 ARE NOT APPLICBLE TO THIS
 PROPOSED BUILDING AS THE MEAN ROOF
 HEIGHT EXCEEDS THE LEAST HORIZONTAL
 DIMENSION.
 PROVIDE CALCULATIONS IN ACCORDANCE WITH
 ASCE 7-98 AT TIME OF PERMIT APPLICATION.
  
 THE PLANS DO NOT SHOW THE ATTIC ACCESS
 AND ATTIC VENTILATION IN ACCORCANCE
 WITH FBC 2309.6 & 2309.7.
  
 DESIGN LOADS FOR THE FLOOR TRUSSES ARE
 NOT SHOWN.
  
 SECTION B/A3 SHOWS A 1 1/2" THRESHOLD AT
 THE SECOND FLOOR STAIR - DOOR. A
 MAXIMUM 1/2" IS ALLOWED BY FBC 1012.1.3.
  
 THE OPENING BENEATH THE EXTERIOR STAIR
 IS REQUIRED TO BE FIRE RATED BY FBC
 1006.2.4.