Plan Review Notes
Plan Review Notes For Permit 03011220
Permit Number 03011220
Review Stop P
Sequence Number 1
Notes
Date Text
2003-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) SHT P-2.51 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTOR SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 AT THE TOP OF THE RISER IN CEILING AS
 SHOWN. PDI-WH 201 & MANUF. INFORMATION.
 2) SHT P-2.51 REMOTE GARAGE, NO ARCH.
 PLANS SHOWN FOR REMOTE GARAGE. PLEASE
 CLAIRFY.
 3) SHT P-2.51 BACKFLOW REQUIRED ON WATER
 SERVICE.
 4) SHT P-2.51 IF THIS BATHHOUSE IS FOR
 A POOL THEN THE PLANS SHALL BE ROUTED TO
 THE COUNTY HEALTH DEPT. 901 EVERNIT ST
 W.P.B.
 5) SHT P-2.51 A RINSE OFF SHOWER IS RE-
 QUIRED MAXIMUM 20' FROM NEAREST WATERS
 EDGE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377