| Plan Review Notes For Permit 03011211 |
| Permit Number |
03011211 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-08-05 00:00:00 | BUILDING PROVISO | | | | | | 1) SUBMIT ENGINEERING FOR THE BOW WINDOW | | | WALL ASSEMBLY WHICH SPECIFIES HOW THE | | | DEAD LOAD FROM THE MULLION AND UPPER | | | WINDOW WALL WILL BE SUPPORTED. THE | | | PRODUCT APPROVAL FOR THE WINDOW WALL | | | SYSTEM DOES NOT INDICATE THAT THE FRAMES | | | AND WINDOWS ARE CAPABLE OF SUPPORTING | | | ANY DEAD LOAD FROM ABOVE. THIS IS TO BE | | | SUBMITTED FOR APPROVAL PRIOR TO THE | | | FRAMING INSPECTION. |
|